MERCURY 5KVA INVERTER PURE SINE WAVE MODEL

769,800.00

DSP technology for fast & smooth charging
Auto Sense intelligent charging (ASIC) adjustment
Highly robust & reliable ideal for computers
User selectable charging current
Wide charging voltage range
Low battery Warning
Overload warning
Main fuse blown protection
Short circuit protection

Out of stock

  Ask a Question

No worries | 100% Money Back Guarantee

  • 7 days easy returns
  • Order yours before 2.30pm for same day dispatch
Guaranteed Safe Checkout

MERCURY 5KVA INVERTER PURE SINE WAVE MODEL M5000

The Mercury 5KVA Inverter Pure Sine Wave with  UPS functionality is a generation ahead of the entire category. That’s because our breakthrough chip-embedded sine wave’ technology delivers the same current as you get from your mains.  The distinguishing features of this Mercury 5KVA inverter Pure Sine Wave  are:

  • DSP technology for fast & smooth charging
  • Auto Sense intelligent charging (ASIC) adjustment
  • Highly robust & reliable, ideal for computers
  • User selectable charging current
  • Wide charging voltage range
  • Low battery Warning
  • Overload warning
  • Main fuse blown protection
  • Short circuit protection

Specification

Voltage Range 180 VAC – 265VAC ± 5 VAC (UPS Mode)
100 VAC – 280 VAC ± 15 VAC (NOR Mode)
Line Low Detection 180V ± 5V (UPS Mode) / 100V ± 15V (NOR Mode)
Line Low Comeback 190V ± 5V (UPS Mode) / 110V ± 10V (NOR Mode)
Line High Detection 265V ± 5V (UPS Mode) / 280V ± 15V (NOR Mode)
Line High Comeback 255V ± 5V (UPS Mode) / 270V ± 10V (NOR Mode)
Frequency Transfer Input Frequency 45-55 Hz

Characterstics (AC)

Inverter Full Load Power  4000
Power Factor 0.8 factor (on resistive load)
On-Line Mode Sine Wave
Battery Mode Sine Wave
On-Line Output voltage Follow the Line Voltage
Battery Mode Output Voltage 200 VAC ± 10%
Transfer Time (No-Load) <15 ms
Frequency at Battery Mode 50 Hz ± 1 Hz

Characterstics (DC)

DC Supply Voltage 48V
Battery Floating Charge Voltage 54.0 VDC ± 0.8 VDC
Charge Current <15 A
Battery Voltage Low Alarm 42.4 VDC ± 0.8 VDC
Battery Discharge Protection 41.6 VDC ± 0.4 VDC
Over Charge Protection > 60.0 VDC ± 0.8 VDC